Phone: (412) 431-4600 Fax: (412) 431-3792
|
TC8 1/8 DIN controller |
Dimensions 1/8 Din ( 48 x 96 x
116 ) Relay or SSR output selectable jumper Up to 3 independent alarms programmable as process alarms, band alarm or deviation alarm Readout programmable from -1999 to 3999 (for linear outputs only)
|
| Specifications | Alarms | Indicators |
| Case PC/abs black Self extinguishing
degree Dimensions Weight Power supply
|
This temperature controller
can be equipped with 3 independent outputs programmable as: * Heating + alarm 1 + alarm 2 In addition to the standard outputs, another optional output is available to perform alarm 3 output functions. Alarm indications: Alarm outputs:
|
°C Lit when the process variable is shown in degrees Celsius °F SMRT OUT1 OUT2 OUT3 OUT 4 SP2 MAN |
| Front
Panels: IP 54 front protection according to IEC 529 CEI 70-1) Installation: Panel mounting with tie rods. Controller held in case with safety screw (TC 8)., Rear terminal board: With screw terminals, connection diagram and safety rear cover Power consumption: 8 VA Insulation resistance: >100 MW (IEC 348) Isolation voltage: 1500 V rms (IEC 348) Common mode rejection ratio: 120 dB 0/60 Hz Normal mode rejection ratio: 60 dB 0/60 Hz Noise rejection: High frequency electromagnetic noises: (IEC 801-4 level 3) Electric discharge: 8 kV (IEC 801-2 |
D/A conversion: Dual slope integration Sampling time: Accuracy: Operating temperature: Storage temperature: Humidity: Protections: |
MEASURING INPUTS
All the inputs are factory calibrated and selectable by front keyboard.
| Thermocouples |
| Type: J, K, L, R, S and N are key board programmable Engineering unit: Burnout: |
Cold junction: Automatic compensation for an ambient temperature between 0 and 50°C Cold junction compensation error: Input impedance: Calibration: |
| Standard Ranges Table |
TC Type |
Range |
TC Type |
Range |
| L | 0-400 °C | S | 0-1760 °C |
| L | 0-900 °C | L | 0-1650 °F |
| J | 0-400 °C | J | 0-1830 °F |
| J | 0-1000 °C | K | 0-2190 °F |
| K | 0-400 °C | N | 0-2550 °F |
| K | 0-1200 °C | R | 0-3200°F |
| N | 0-1400 °C | S | 0-3200 °F |
| R | 0-1760 °C |
NOTE: To increase the
sensibility of the control parameters, a TC input
measuring range with a minimum span of 300°C or 600°F can be selected
within the standard input range.
| RTD input |
| RTD type: Pt 100 3 wires connection Calibration: Line resistance: |
Engineering unit: °C and °F keyboard programmable Burnout: |
Standard Range Table |
| °C | °F |
| -199.9 - 400 | -199.9 - 400 |
| -200 - 800 | -330 - 1470 |
NOTE: To increase the sensibility of
the control parameters, an RTD input
measuring range with a minimum span of 100°C or 200°C can selected
within the standard input range.
| mA and V inputs |
| mA input (standard): 0-20 mA and 4-20 mA keyboard programmable Input impedance: <5W V input: |
Input impedance: >400 kW 0-60 mV and 12-60 mV programmable. Input impedance: > 1 MW Readout: Decimal point: |
| Standard Range Table |
| Input | Impedance | Input | Impedance |
| 0-20 mA | <5W | 0-5 V | >200 kW |
| 4-20 mA | <5W | 1-5 V | >200 kW |
| 0-60 mV | >1 MW | 0-10 V | >400 kW |
| 12-60 mV | >1 MW | 2-10 V | >400 kW |
LOGIC INPUTS
Both the TC8 and TC 16 can be equipped with a logic input
for selecting between main set point and auxiliary set point
(SP or SP2)
SET POINTS
Two set points are available:
Main set point (SP)
Auxiliary set point (SP2)
Set point transfer:
Transfer from SP to SP2 and vice versa may be driven by logic
input (contact closure). The transfer may be done by a step
transfer or by a ramp with two different programmable rates of
rise (ramp up and ramp down).
Set point limiters:
Set point low limit and set point high limit are programmable.
| CONTROL ACTION |
| Algorithm: PID + SMART Type: Proportional band: Hysteresis (for ON/OFF control
action): Integral time: Derivative time: Integral preload: |
Out 1 (heating) cycle
time: From 1 second to 200 seconds AUTO/MANUAL
mode: AUTO/MANUAL transfer: Two control outputs Cooling cycle time: Overlap/dead band: |
NOTE: When the proper cooling medium
(air, oil or water) is set during the
configuration procedure, the temperature controller will automatically set
the 2 output parameters.
| CONTROL OUTPUTS |
| Type: Time proportioning Direct/reverse
action: Output level indication: Output status indication: Output level limiter: |
Relay Outputs Output cycle time: Programmable from 1 s to 99 s Output
1 (heating): Output2 (cooling): Logic voltage for SSR driver (output 1
only): Output safety value: |
| OUTPUT "TURN OFF" FUNCTION |
| This function disables the control output, making the temperature controller operate as an indicator. As a result, the process variable can be monitored even when the load is OFF. When the control mode is resumed, the integral component of the output signal will be set to zero and the soft start and the alarm masking functions will be enabled. |
| ALARMS | |
| Output action: Direct or reverse function programmable Alarm functions: Alarm reset: |
Alarm masking: Each alarm can be configured as masked alarm or standard alarm. This function eliminates false indication at instrument start-up and after set point change |
| Process alarm Operational mode: High or low programmable Threshold: Hysteresis: Band alarm Threshold: Hysteresis: |
Deviation alarm Operational mode: High or low programmable Threshold: Hysteresis: Heater breakdown alarm: Type: Threshold: |
Keyboard description
|
Upper display Shows the actual measured value or the selected parameter value. Lower display shows: |
|
TC16 1/16 DIN controller |
Dimensions 1/16 DIN (48 x 48 x
122) Up to 2 independent alarms
programmable as process Configured by front keyboard |
| Specifications | Alarms | Indicators |
| Case PC/abs black Self extinguishing
degree: Dimensions Weight Power supply
|
This temperature controller
can be equipped with 2 independent outputs programmable as: * Heating + alarm 1 * Heating + cooling An optional output is available to perform alarm 2 and/or the HBD alarm output. Alarm indications: Alarm outputs:
|
SP2 Flashing slowly when SP2 is used. SMRT MAN °C/°F OUT1 OUT2 OUT3 Flashing slowly when the heater current is lower than the programmed threshold (HBD). Flashing quickly when the HBD alarm and alarm 2 are simultaneously on |
| TC8 and TC16 controllers Main Features |
| * IP 543
front protection *SMART function for self-tuning of control parameters *Proprietary algorithm for heating/cooling control with automatic setting of control parameters according to the cooling media (air, oil or water) *Dual 4-digit LED display *Universal input (6TC types, RTD, mV, mA, 5Vand 10V all calibrated) *Independent alarms programmable as process alarm, band alarm or deviation alarm *Automatic or manual alarm reset *Alarm masking during start-up or set-point change *Manual control mode *2 programmable set points (main and auxiliary) *2 independent ramps (up and down ramps) for set point changes *Logic input for set point selection *Switching power supply (100 to 240 VAC) *Soft start ( time out output limiter) *Output power limit on maximum if rise function *Output "turn off" function
During start-up the SMART function implements auto-tuning, calculating the value of the P.I.D. parameters to optimize the set point approach. During control SMART implements self-tuning, updating the P.I.D. parameters according to the type of response due to a set point change as load change |
![]() Soft
Start
|
How to Order
Specify the six-digit number for the desired model.
| TC8 087650 TC8 Temperature Controller 1/8 DIN size controller with universal analog input, SMART self-tuning, 1 time proportioning or ON/OFF relay type or SSR type control output, 2nd relay type output for alarming or cooling control, 3rd relay output for alarm 2, and a digital input to select SP/SP2. 087651
|
TC16 087660 TC16 Temerature Controller 1/16 DIN size controller with universal analog input, SMART self-tuning, 1 time proportioning or ON/OFF relay type control output, 2nd relay type output for alarm 1 or cooling control and a 3rd relay output for alarm 2. 087661 087662 |
Call 412-431-4600
Fax 412-431-3792
or email your request